Description:
Fused and non-fused enclosed Rotary Disconnect Switches from 16 to 1200A in NEMA 1, 3R, 4, 4X, 12 enclosures.
Features
• UL 98 Listed for general purpose, main disconnect, or branch circuit protection up to 600Vac/dc
• UL 508 Listed for motor disconnect applications up to 600Vac
• Multiple field installed accessories enhance the enclosed disconnect switches to fit the desired application
• Lockout/tagout: Up to three 1⁄4˝ shank padlocks can be installed on external handles
Ratings:
• Volts: 600Vac; 250-600Vdc*
• Amps: 16-1200A
• Short-Circuit Current Ratings: UL 98: 25kA-200kA; UL 508: 10kA-65kA
*Some non-fused disconnect switches are not rated for DC applications.
Specifications
• Operating temperature: -20ºC to 70ºC
• 4X Plastic Enclosure Flammability Rating:
Polycarbonate UL 94-5VA-0
Fiberglass UL 94-5V
Agency Information
• UL 98 Listed: File E182262, Guide WIAX, WIAX7
• UL 508 Listed: File E155129, Guide NLRV, NLRV7
• cULus Listed to CSA Standard 22.2, No. 14
• cULus Listed to CSA Standard 22.2, No. 4
• Conforms with IEC 60947-3
• CE Compliant
• RoHS Compliant
Field Installed Accessories
• Auxiliary contacts
• Terminal shrouds
Available Cooper Bussmann Fuses
3-Pole UL 98 600Vac
Class | Type |
CC | LP-CC Time-Delay, Current Limiting |
CC | FNQ-R Time-Delay |
CC | KTK-R Fast-Acting |
J | LPJ Time-Delay, Current Limiting |
J | JKS Fast-Acting Fuses |
J | DFJ High Speed Drive Fuse |
L | KRP-C Time-Delay, Current Limiting |
L | KTU Fast-Acting |
L | KLU Time-Delay |
3-Pole UL 98 600Vac
Part Numbers
All part numbers provided with integral or installed lugs and a black selector handle.
All part numbers provided with integral or installed lugs and a black selector handle.
Order red/yellow handle by changing the suffix “B” to “R.”
(1) Enclosures ≤100A are polycarbonate, flammability rating UL 94-5VA-V0, ≥200A are fiberglass, flammability rating UL 94-5V.
Switch Ratings
Enclosure Weights - Lbs & Dimensions - in
Available Field-Installed Accessories - Order Separately
UL General Purpose Amp Rating |
Fuse Type |
NEMA Enclosure Type & Part Number | |||||
1 | 3R | 4 | 4X Plastic(1) | 4X Stainless | 12 | ||
30 | J | ER1-30J3PB | ER3R-30J3PB | ER4-30J3PB | ER4P-30J3PB | ER4X-30J3PB | ER12-30J3PB |
60 | J | ER1-60J3PB | ER3R-60J3PB | ER4-60J3PB | ER4P-60J3PB | ER4X-60J3PB | ER12-60J3PB |
100 | J | ER1-100J3PB | ER3R-100J3PB | ER4-100J3PB | ER4P-100J3PB | ER4X-100J3PB | ER12-100J3PB |
200 | J | ER1-200J3PB | ER3R-200J3PB | ER4-200J3PB | ER4P-200J3PB | ER4X-200J3PB | ER12-200J3PB |
400 | J | ER1-400J3PB | ER3R-400J3PB | ER4-400J3PB | ER4P-400J3PB | ER4X-400J3PB | ER12-400J3PB |
600 | J | ER1-600J3PB | ER3R-600J3PB | ER4-600J3PB | ER4P-600J3PB | ER4X-600J3PB | ER12-600J3PB |
800 | L | ER1-800L3PB | ER3R-800L3PB | ER4-800L3PB | ER4P-800L3PB | ER4X-800L3PB | ER12-800L3PB |
Switch Ratings
Switch Amp Rating |
Disconnect Switch |
Fuse Type |
No. of Poles |
Voltage |
SCCR @ Vac |
Max Hp Rating @ 600Vac |
|
Vac | Vdc | ||||||
30 | RDF30J-3 | J | 3 | 600 | 250 | 200kA | 20 |
60 | RDF60J-3 | J | 50 | ||||
100 | RDF100J-3 | J | 75 | ||||
200 | RDF200J-3 | J | 150 | ||||
400 | RDF400J-3 | J | 350 | ||||
600 | RDF600J-3 | J | 600 | 500 | |||
800 | RDF800L-3 | L |
Enclosure Weights - Lbs & Dimensions - in
Part Number Family |
Amp Rating |
Fuse Type |
NEMA Enclosure Type | H x W x D | Mounting Centers H x W |
Weight Lbs |
||
A | B | C | ||||||
ER_-30J | 30 | J | 1, 3R, 4, 12 | 10x10x6 | 8.3x8.3 | 15 | ||
4X-SST | 10x10x6 | 9.5x8.3 | 8.3x9.5 | 15 | ||||
4X-Plastic(1) | 12x10x6 | 12x5.6 | 7.64x10 | 8 | ||||
ER_-60J | 60 | J | 1, 3R, 4, 12 | 12x10x6 | 10.3x8.3 | 19 | ||
4X-SST | 12x10x6 | 11.5x8.3 | 10.3x9.5 | 19 | ||||
4X-Plastic(1) | 13x13x6 | 14x7.6 | 9.6x12 | 11 | ||||
ER_-100J | 100 | J | 1, 3R, 4, 12 | 14x12x6 | 12.3x10.3 | 21 | ||
4X-SST | 14x12x6 | 13.5x10.3 | 12.3x11.5 | 21 | ||||
4X-Plastic(1) | 13x13x6 | 14x7.6 | 9.6x12 | 12 | ||||
ER_-200J | 200 | J | 1, 3R, 4, 12 | 24x20x8 | 22x18.1 | 55 | ||
4X-SST | 24x20x8 | 23.2x18.1 | 22x19.3 | 55 | ||||
4X-Plastic(1) | 27x21x10 | 25.75x14 | 39 | |||||
ER_-400J | 400 | J | 1, 3R, 4, 12 | 48x36x12 | 45.75x34.9 | 188 | ||
4X-SST | 48x36x12 | 46.9x34.9 | 45.75x36.1 | 188 | ||||
4X-Plastic(1) | 51x37x14 | 50.1x28.5 | 186 | |||||
ER_-600J | 600 | J | 1, 3R, 4, 12 | 48x36x12 | 45.75x34.9 | 216 | ||
4X-SST | 48x36x12 | 46.9x34.9 | 45.75x36.1 | 216 | ||||
4X-Plastic(1) | 51x37x14 | 50.1x28.5 | 214 | |||||
ER_-800L | 800 | L | 1, 3R, 4, 12 | 48x36x12 | 45.75x34.9 | 216 | ||
4X-SST | 48x36x12 | 46.9x34.9 | 45.75x36.1 | 216 | ||||
4X-Plastic(1) | 51x37x14 | 50.1x28.5 | 214 | |||||
(1) Enclosures ≤100A are polycarbonate, flammability rating UL 94-5VA-V0, ≥200A are fiberglass, flammability rating UL 94-5V. |
Available Field-Installed Accessories - Order Separately
Auxiliary Contacts - for 30 to 800 Amp Switches | ||||||
Contact | Number of | Continuous | Voltage | Max Number of Aux | Part | |
Type | Contacts | Amp Rating | Rating | Contacts per Switch | Number | |
NO | 1 | 10A | 600Vac | 30 to 200A: 4 | BAC05 | |
NC | 1 | 10A | 600Vac | 400 to 800A: 8 | BAC06 |
Terminal Shrouds - for 200 to 800 Amp Switches - includes terminal shroud for lineside or loadside | ||||||||
Switch Amp rating | Number of Poles | Part Number | ||||||
200 | 3 | TSH8-3TB | ||||||
400 | 3 | TSH9-3TB | ||||||
600-800 | 3 | TSH10-3TB |