cooper bussmann

WCF_RN-Wind CUBEFuse for Wind Power Generation Applications

  

Fast-acting 690 volt CUBEFuse specifically designed to protect low-fault current conditions that occur in wind power generation systems.

The finger-safe feature minimizes exposure to live parts to reduce hazard to personnel and utilizes the integral 690 volt CUBEFuse holder to minimizes footprint.

The Wind CUBEFuse minimizes incident energy and reduces arc flash hazards utilizing Class J electrical characteristics and is UL 248 Recognized for low voltage fuses.
 

Catalog Symbol: WCF_RN
 
Description:
Finger-safe, fast-acting CUBEFuse for wind power generation.
 
Electrical Characteristics:
Maximum clearing time at 200% 
 
rated current:
• 4 Minutes for 1 to 30A fuses
• 6 Minutes for 35 to 60A fuses
• 8 Minutes for 70 to 100A fuses
 
Agency Information:
• UL Recognized Fuse: Guide JFHR, File E56412
• cURus component certified C22.2
 
Other Ratings/Specifications:
Watts Loss at Rated Current: WCF15RN: 3.48W
WCF30RN: 5.45W
WCF60RN: 7.27W
WCF100RN: 11.50W
 
Operating and Storage Temperature Range: -40 to 90°C
 
Material Specifications:
• Case: Glass filled PES (Polyethersulfone)
• Terminals: Copper alloy
• Terminal plating: Electroless tin 
 
Installation:
Fits 690V WCF holders as listed in the table
 
Application:
• Wind Systems:
- Transformer protection
- Pitch and speed control
- Turbine HVAC and lighting

Carton Quantity and Weight
Amp
Rating
Carton
Qty.
Weight Per Carton
lbs kg
WCF1-30A 12 1.39 0.63
WCF35-60A 12 1.42 0.65
WCF70-100A 6 1.74 0.79


Catalog Numbers (amp rating)
Non-Indicating Wind CUBEFuse
WCF1RN WCF20RN WCF45RN WCF90RN
WCF3RN WCF25RN WCF50RN WCF100RN
WCF6RN WCF30RN WCF60RN  
WCF10RN WCF35RN WCF70RN  
WCF15RN WCF40RN WCF80RN  


Features and Product Benefits
• Maximize uptime and reliability using fuses designed and recognized to UL 248 for low voltage fuses
• Fast-acting protection specifically designed for low-fault current conditions that occur in wind power generation systems
• Minimize chances of equipment failure and personnel injury when using full range fuses having fast response time to low-magnitude faults
• Simplify compatibility with readily available industry standard Class CF holders while minimizing panel space by up to 80%
• Meets all UL specified overload opening requirements
• Minimizes incident energy and reduces arc flash hazards utilizing Class J electrical characteristics
• Finger-safe feature minimizes exposure to live parts, reducing hazard to personnel

WCF_RN Dimensions – in (mm)



Time-Current Characteristic Curves–Average Melt


Current Limitation Curves


Wind CUBEFuse Holders
Catalog Numbers(amps) Fits 690V Wind CUBEFuse Holder
WCF1RN TCFH30NW TCFH60NW TCFH100NW
WCF3RN X X X
WCF6RN X X X
WCF10RN X X X
WCF15RN X X X
WCF20RN X X X
WCF25RN X X X
WCF30RN X X X
WCF35RN   X X
WCF40RN   X X
WCF45RN   X X
WCF50RN   X X
WCF60RN   X X
WCF70RN     X
WCF80RN     X
WCF90RN     X
WCF100RN     X
All 690V 100, 60 and 30A Wind CUBEFuse holders can be dovetail together for the required number of poles. 
 
----------------------------------
伊顿 EATON|Bussmann规格资料查询
伊顿 EATON|Bussmann产品规格类型
或许您会感兴趣...
联系客服
深圳市博孚美科电子有限公司
总机: 0755-82862885, 82862629
传真: 总机 转 801
邮箱: service@bussmann.net.cn
网址: http://www.bussmann.net.cn
资料中心: http://bm-bussmann.com