Description:
BS 88 style stud-mount fuses.
BS 88 style stud-mount fuses.
Ratings:
Volts: 690Vac/500Vdc
Amps: 400-700A
IR: 200kA RMS Sym.
Agency Information:
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized.
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Features and Benefits
• Excellent cycling capability
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Dimensions (mm)
Catalog Numbers
• Watts loss provided at rated current.
Time-Current Curve
Peak Let-Through Curve
Dimensions (mm)
Catalog Numbers
Catalog Numbers | Type | Rated Current RMS-Amps | I2t(A2 Sec) | Watts Loss | ||
Pre-arc | Clearing | |||||
at 415V | at 660V | |||||
400FMM 450FMM 500FMM 550FMM 630FMM 700FMM |
FMM |
400 450 500 550 630 700 |
10000 15000 20000 30000 45000 60000 |
40000 60000 82000 120000 180000 245000 |
72500 105000 150000 215000 310000 420000 |
85 90 100 100 100 120 |
Time-Current Curve
Peak Let-Through Curve