Description:
BS 88 style stud-mount fuses.
BS 88 style stud-mount fuses.
Ratings:
Volts: 690Vac/500Vdc
Amps: 6-710A
IR: 200kA RMS Sym.
Agency Information:
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. 350Vdc (IEC) rating. Consult Cooper Bussmann for UL Recognition status.
CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. 350Vdc (IEC) rating. Consult Cooper Bussmann for UL Recognition status.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics.
The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Features and Benefits
• Excellent cycling capability
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Dimensions (mm)
Catalog Numbers
Catalog Numbers | Type | Rated Current RMS-Amps | I2t(A2 Sec) | Watts Loss | ||
Pre-arc | Clearing | |||||
at 415V | at 660V | |||||
180MMT 200MMT 225MMT 280MMT 315MMT 355MMT 400MMT 450MMT 500MMT 560MMT 630MMT 710MMT |
MMT |
180A 200A 225A 280A 315A 355A 400A 450A 500A 560A 630A 710A |
1650 2200 3700 6600 8600 13500 21000 30000 42000 60000 68500 78000 |
12000 16000 26000 47000 62000 97000 150000 220000 300000 430000 500000 600000 |
18000 23000 40000 70000 91000 140000 220000 320000 450000 640000 720000 850000 |
42 42 42 47 51 54 60 57 64 64 86 105 |
Time-Current Curve
Peak Let-Through Curve
总机: 0755-82862885, 82862629
传真: 总机 转 801
邮箱: service@bussmann.net.cn
网址: http://www.bussmann.net.cn