Description:
Ferrule style high speed fuses.
Ferrule style high speed fuses.
Ratings:
Volts: 1000Vac/800Vdc
Amps: 20-30A
IR: 25kA RMS Sym. 20kA@ 800Vdc
Agency Information:
CE, UL Recognized
CE, UL Recognized
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
Dimensions - mm (inches)
Catalog Numbers
Electrical Characteristics | Ordering Information | ||||||
Size |
Rated |
I2t (A2S) |
Watts Loss |
Part Number |
Carton Qty. |
Carton Weight (kg) |
|
Pre-arc |
Clearing at 1000V |
||||||
14 x 67mm (9/16") |
20 25 30 |
25 33 52 |
220 350 450 |
9 11 14 |
FWJ-20A14F FWJ-25A14F FWJ-30A14F |
10 | 0.3 |
Fuseclips:
• Catalog Number: 5591
Time-Current Curve
Peak Let-Through Curve